| Environmental Conditions |
|
|
| Altitude |
0 ft to 10000 ft Operating |
| Altitude |
0 ft to 50000 ft Storage |
| Humidity |
5 to 95% Relative Humidity Operating |
| Humidity |
5 to 95% Relative Humidity Storage |
| Temperature |
-13°F (-25°C) to 149°F (65°C) Storage |
| Temperature |
23°F (-5°C) to 113°F (45°C) Operating |
| General Information |
|
|
| Brand Name |
APC |
| Manufacturer Website Address |
www.apc.com |
| Description |
The American Power Conversion (APC) Metered Rack Power Distribution Unit (PDU) distributes power to devices in the rack. It has a sensor that measures the current used by the PDU and its attached devices. It can be monitored through Web, Telnet, SNMP, SSH, or InfraStruXure Manager interfaces. |
| Product Line |
Metered Rack |
| Product Type |
PDU |
| Miscellaneous |
|
|
| Additional Information |
Alarm Thresholds Flash Upgradeable Horizontal Mounting Capability Local Current Monitoring Display Network Management Remote Current Monitoring Remote Management Capabilities |
| Certifications & Standards |
cUL Listed CSA FCC Part 15 Class A ICES-003 UL 60950 UL Listed |
| Package Contents |
Metered Rack 30A PDU Cord Retention Bracket(s) Installation Guide Rack Mounting Brackets User Manual |
| Physical Characteristics |
|
|
| Dimensions |
3.48" Height x 17.47" Width x 4.41" Depth |
| Form Factor |
2U Rack-mountable |
| Power Cord/Cable |
12 ft |
| Weight (Approximate) |
7.40 lb |
| Power Description |
|
|
| Current |
24 A Derated Input Current |
| Current |
24 A Total Current Draw Per Phase |
| Current |
30 A Input Current Per Phase |
| Frequency |
50 Hz |
| Frequency |
60 Hz |
| Input Voltage |
208 V AC |
| Output Voltage |
208 V AC |
| Technical Information |
|
|
| Input Receptacles |
NEMA L6-30P |
| Output Receptacles |
12 x IEC 320-C13 |
| Output Receptacles |
4 x IEC 320-C19 |
| Protection Type |
Overload Protection |
| Warranty |
|
|
| Standard Warranty |
2 Year |